
Application: Pump Test station ventilation required operator breathing zone isolation.
Dust/Fume Type: MEK Fumes and chemical vapors
Location: Colorado
Ventilation Equipment Solution Selection: (1) – Industrial blower, non-sparking construction.
Airflow/static pressure: 900 cfm @ 4” s.p.

Application Solution: Existing position modified to enclose work area with new sheet metal enclosure and lighting. Fume generation points were source captured with local hoods and pick points with a new exhaust fan installed on the roof.
Operator breathing zones were isolated and exhaust air was reduced to 900 cfm with source capture from 2400 cfm from general exhaust plan.